Connecting to a Cutler-Hammer SVX9000 or an HVX9000
Adjustable Frequency Drive

SVX9000

9000XDrive is a PC Based Software commisioning tool for use with SVX9000 or HVX9000 Variable Frequency Drives

This program can upload and download parameter files to and from the VFD

You can also monitor live data from the VFD

You can control the VFD with Stop/Start and Speed functionality

Also, the fault history can be downloaded with statistics available from the time of the fault.  Items that are saved at the time of the fault are:  Motor Current, Motor Voltage, VFD Temperature, DC Bus Voltage, Output Frequency and more.

The cable used to connect to the VFD is a 9 pin serial cable using only pins 2, 3 & 5.  This is very important because if you use a cable with any other pins connected, you may harm your PC.  This port on the VFD also has voltage on other pins that supplies power to the Keypad on the front of the drive.

The program is available here:
9000XDrive
(Version 2.0.11)

Release Notes

Each VFD also has an Application file associated with it.  These application files also need to be in the
C:/AFEngine/Applications folder.

Here are the Application files:

SVX00031V013.VCN
SVX00031V014.VCN
SVX00031V015.VCN
SVX00031V016.VCN
SVX00031V017.VCN
SVX00031V018.VCN
SVX00031V019.VCN
SVX00031V020.VCN
HVCHST02V809.VCN
HVCHST02V911.VCN
HVCHST02V1113.VCN
HVCHST02V1521.VCN

Below are some manuals for more information: